Thursday November 09 2006
Fine Tuning Forced-Air Heat
Use two-stage equipment and zone dampers to increase efficiency, comfort,
and customer satisfaction
Hydronic, or hot water, heating has been standard for years in many parts of
the U.S. It is seeing a surge in popularity at present, mainly because of the
increasing use of radiant floor heating, which is known for providing even,
comfortable heat. Yet contrary to popular belief, not every home in the free
world needs hydronic heat to achieve this level of comfort.
Hydronic heat is sometimes touted as more comfortable than forced-air heat.
But since the typical hydronic system is significantly more expensive than the
typical hot-air system -- especially if cooling is included -- this is an
apples-to-oranges comparison. Customers willing to invest in a quality hot-air
system, rather than a bare-bones package at the lowest price, will find that
forced hot air can be as comfortable as hydronic heating.

The least expensive forced-air system usually includes a single-stage
furnace with a single-speed blower motor. The entire house is ducted as a
single zone, and therefore has just one thermostat. If the system is sized by a
contractor who uses a rule-of-thumb formula to estimate heat loss and heat
gain, the homeowner can end up paying high energy bills for a noisy,
inefficient system that provides uneven temperatures from room to room.
A quality forced-air system would probably include a two-stage furnace with
a variable-speed blower motor. The house would be separated into several zones
with separate thermostats, and the air would be distributed through
well-sealed, insulated ducts. In many cases, such an upgraded hot-air system
will still cost less than a hydronic system.
One of the most important steps to designing a quality heating and cooling
system is to take the time for a long talk with the homeowner. Don't assume
that you know what the customer wants and is willing to pay for. Most
homeowners are not aware of all the available options. Here are some of the
questions you need to ask:
This
is a tough one to get answered. Often the answer is, "Gee, I really have no
idea." However, someone building a 2,500-square-foot home with a $7,000 budget
is not looking at the same system as a person with a $12,000 budget.
What type of system do you have now, and what do you like and dislike
about it? The answer to this question will tell you what the customers
expect from their new system. Different customers have different priorities
when it comes to efficiency, comfort, noise, and ease of operation.
Does anyone in the home have allergies? If the answer is yes,
the customer may want to consider a high- performance air filter. There are
three basic types of high-performance air filters: electrostatic air cleaners
(about $100 to $150 installed), pleated media filters ($275 to $325), and
electronic air cleaners (about $625 to $700).
What type of fuel is available at your site, and what fuel do you
prefer? If a client has a phobia about gas or an aversion to oil or
heat pumps, you should know about it before you design their system.
Finally, you need to explain to the homeowner what your standard design
temperatures are -- for example, 70?F inside on a 0?F day, and 75?F
inside on a 95?F day. Make sure you're in agreement on these parameters up
front, and if they have other ideas, incorporate them into your design, as long
as their ideas are reasonable.
Heating contractors vary in their attention to detail. Ask your prospective
heating sub how load calculations and duct design are performed; the answers
will help you evaluate the sub's expertise.
Does your heating
contractor calculate accurate room-by-room heating and cooling loads? In order
to perform these calculations, your sub needs to know the insulation values of
the floor, walls and ceiling; the R-value of the windows; and the orientation
and measurements of any skylights (see "Trouble-Free Forced Air Heat," 12/98).
Many heating contractors still use rule-of-thumb square foot formulas for
calculating heating and cooling loads. But since glass-to-wall ratios can
differ significantly from one floor plan to the next, "square-footing it" is a
dangerous practice.
Duct design. Heating subs vary in their level of attention to
duct design (see "Duct Design Basics," 12/95). The standard duct design manual
is Manual D -- Residential Duct Systems from the Air Conditioning Contractors
of America (ACCA, 1712 New Hampshire Ave. N.W., Washington, D.C. 20009;
202/483-9370; ).
One basic duct design error is inadequate return ductwork. A system with
multiple return grilles is preferable to a system with a single, central return
grille. Another basic error is supply ductwork that is not matched to the
output of the furnace. In extreme cases, undersized ductwork is unable to
remove the furnace's heat fast enough, causing the heat exchanger to overheat
and crack.
Supply air vents should be placed where they can deliver air along the
exterior perimeter walls, where the greatest heat loss and gain occurs. Avoid
low sidewall supplies, which can cause drafts and result in dissatisfied
customers.
The calculated loads will show the Btus per hour (Btu/h) required at peak load
conditions (the coldest outdoor temperatures in winter and the hottest outdoor
temperatures in summer). In most areas, peak conditions are reached only for a
few hours in a typical season. So most of the time, a correctly selected unit
is oversized for moderate conditions. That's why it's important to offer the
customer a two-stage system.
|
Figure 1. Two-stage gas furnaces, like this model from Goettl Air
Conditioning, have two levels of Btu output and airflow. Since low stage
operation is adequate to meet the heating demand most of the time, such units
are quieter and more efficient than single-stage furnaces. |
Two-stage models are available in mid-efficiency and high-efficiency gas
furnaces, as well as air-source and geothermal heat pumps (see Figure 1). These
units offer "Btu staging" -- for example, a two-stage gas furnace might have a
65,000 Btu/h input on low, and a 100,000 Btu/h input on high.
If you burn oil, you probably will be limited to choosing a single-stage
furnace. While gas burners can be equipped with a two-position gas valve, an
oil burner is equipped with a unique nozzle that is optimized for a single
firing rate. Two-stage oil pumps are usually not available for residential
furnaces.
In heating mode, two-stage units operate at low speed for 80% of the time.
Two-stage units quietly deliver consistent indoor comfort through longer run
cycles at lower speed than conventional single-speed systems. A typical furnace
allows the air temperature in a space to fluctuate up to 4?F, while a
two-stage system reduces the temperature fluctuation to less than 2?F,
while improving air circulation at the same time.
This has several benefits to the owner. First, two-stage units offer
improved comfort, because of consistent temperatures throughout the zone.
Second, two-stage units are extremely quiet, because their two-speed fans are
usually operating at low speed. Last and most important, operating costs are
lower, because the Btu per hour output is matched more closely to the actual
load, and because the unit fires for longer cycles, reducing the start-up and
shut-down cycles experienced with a single-speed system.
Variable-speed blower motors. A furnace with a variable-speed
blower motor provides improved comfort and efficiency. A variable-speed motor,
which is available for either a gas or oil furnace, slowly ramps up on the
initial call for heat, so that the air-speed increase more closely follows the
increase of heat available at the heat exchanger. Conversely, on the shut-down
cycle, the fan will slowly ramp down, extracting the maximum Btus from the heat
exchanger surface. In contrast, the blower in a standard furnace usually has a
timed on/off control, which can cause an objectionable "cold blow" on start-up
and shut-down.
A variable-speed blower can also be set up to operate at very low "fan-only"
speeds. The fan-only feature, which is controlled by a manual on/off switch at
the thermostat, is especially important for systems with high-performance air
filters, because the only time the air filter will work is when the air is
moving through it.
Fan-only operation may also be useful for a room that is not on a dedicated
zone and is located far away from the thermostat. Constantly introducing new
air into the room will bring the temperature more into line with the
temperature in the rest of the home. The cost of running an efficient
variable-speed blower on fan-only for a year is less than $20, while a standard
motor running for the same year would cost more than $150 to operate.
Two-speed condenser. For the cooling side of the system,
consider upgrading to a two-speed condenser. Homes with skylights and large
window areas will often have very high heat gains on sunny days, dictating the
size of the cooling unit. But on warm, humid days without a bright sun, the
house will not have as much heat gain, and a single-speed condenser will not
run long enough to remove the high humidity.
A two-stage condenser (which usually includes both a two-stage compressor
and a two-speed condenser fan motor) coupled with a variable-speed blower fan
can remove up to 30 times more moisture than a standard fixed-speed system,
because it will not be short-cycling as often.
Some manufacturers use microprocessor technology and humidity sensors to
control the cooling unit. One example is Carrier's Thermidistat, which looks
like any electronic thermostat, but is capable of displaying the outdoor
temperature and indoor relative humidity. It will precisely operate the system
based on desired indoor temperature and humidity set points.
When this control is coupled with matching heat-pump components, it will
regulate the variable-speed fan motor to maintain consistent air discharge
temperatures.
Such systems can provide a minimum air temperature delivery of 100?F, up
to a maximum of over 120?F -- about 20?F warmer than
previous-generation equipment. Most users report higher comfort levels with
these warmer air delivery temperatures.
Many contractors do not recommend or install zoning equipment, due to the
mistaken belief that zoning is complicated. But if the homeowner's lifestyle
requires different temperature levels in different areas, zoning probably makes
sense, especially in larger homes.
Another reason to zone is to provide good temperature control in any area of
the house with much greater heat loss (or gain) than other areas of the house.
Typical examples are areas with many windows or rooms that are oriented toward
a different direction than most of the other rooms in the house (Figure 2).
During your initial meeting with the owner, look for such areas -- for example,
a sunroom or a finished area above a garage.
|
Figure 2. A room with an unusually large area of glass tends to have
high heat loss at night and high heat gain on sunny days. Such a room is a good
candidate for a separate zone. |
How do you decide whether an area needs its own furnace, or just a zone off
the main unit? Assuming you have sufficient capacity, it is usually less
expensive to install (and always less expensive to operate) a zone off of the
main system than to install a separate dedicated unit. In some cases, though,
the location of the zone or the building's total heating and cooling loads may
dictate a separate unit.
When designing a zoned system, the first step is to know the Btu and airflow
demands of the zone. Once the actual air requirements are verified, the
ductwork should be designed and installed at a slightly larger size (10% to 15%
larger) than standard ductwork. Oversizing each zone's ducts helps to dissipate
any extra airflow when only one zone calls for heating or cooling.
|
Figure 3. Motorized zone dampers, like these examples from Jackson
Systems, are available for both round ducts (top) and rectangular ducts
(bottom). |
Zoning is accomplished by installing motorized zone dampers (Figure 3).
Since the premise for zoning is to reduce the air going to the area where the
temperature is satisfied and deliver air to the area that needs the
heating/cooling, each zone will need dampers. Manufacturers of zone dampers
include Carrier, Jackson Systems, and Robertshaw Controls (see "" ).
If there is room for a dedicated trunk line to serve the zone, it is usually
easier and cheaper to install a zone damper in the trunk line. In that case,
the individual branch lines that are tapped off the dedicated trunks will not
require zone dampers. When there is no room for a dedicated trunk line, the
area can be zoned by installing a series of dampers in the branch lines serving
the area, and then controlling the dampers together with a multi-damper
enabler. Usually, the enabler is purchased from the zone damper supplier.
A multi-zone system requires individual thermostats to regulate the
temperatures of each zone. The low-voltage thermostat wire is fed to a main
zone panel. Wires are then run to the equipment and each zone damper. High and
low temperature sensors are usually placed in the supply-air plenum to serve as
unit safeties in the unlikely event of a zone damper failure.
Supply ductwork is the only part of the system with dampers. When one zone
calls and gets supply air, the returns are still being drawn from the entire
home. Therefore it's important to locate adequate returns in each zone.
Two-story homes should have a combination of high and low return grilles.
Extra air. When only one zone in a multi-zone system calls for
heat, there needs to be some way to dissipate the extra cfm output of the
furnace. Some brands of zone control ignore this problem, and let the high
airflow howl through the small duct. Other brands will allow for the other
zone(s) to open slightly and allow for the air to "leak" into areas that do not
actually require conditioning. A third option is to install a bypass damper
that allows the excess air to be recirculated back to the return. How the
"extra" air is handled is a matter of contractor preference. The surplus air
issue is much less of a problem with a two-stage gas furnace or a two-stage
heat pump, especially one with a variable-speed fan -- one more reason for
installing two-stage equipment.
In unconditioned spaces like crawlspaces and attics, use insulated duct for
both supply and returns. For ducts in conditioned spaces, insulation is highly
recommended, but not required. During the cooling season, uninsulated metal
ducts can become cold enough to sweat.
. Many studies have shown
that the typical forced-air system has leaky ductwork. Leaky ductwork wastes
energy dollars and can lead to pressure imbalances in a house. An excellent
resource for information on duct sealing can be found at .
|
Figure 4. Sheet-metal duct joints must be screwed together before mastic
is applied. |
Joints in sheet-metal duct should be screwed together and sealed with mastic
(Figure 4). Using mastic is always good practice, although some contractors
omit mastic on ducts in conditioned spaces. Four water-based duct mastics are
Glenkote 181, Hardcast Versi-Grip 181, RCD, and Uni-Mastic 181 Duct Sealer.
Duct mastic has the consistency of mud and is spread with gloved hands or a
paint brush (Figure 5). Wide gaps in ductwork can be bridged with fiberglass
tape before applying mastic.
  |
| Figure 5. Joints in
sheet-metal duct should be sealed with mastic, which can be applied with a
paint brush (left). When mastic is used on duct board, the joint should first
be bridged with fiberglass tape or scrim (right). |
Joints in rigid fiberglass duct (duct board) should be sealed with a UL-181
heat-activated tape, like Ideal Tape #490 (Figure 6). Heat-activated tape works
better and lasts longer than the aluminum pressure-sensitive tape (See "").
  |
| Figure 6. The
female end of a duct board joint is pulled taut and stapled through to the male
end (left). The joint is completed by applying heat-activated tape, which is
warmed with an Amcraft duct board iron (right). |
Keep flex duct short and fat. Insulated flexible duct is usually much faster
to install than rigid duct. However, flex duct must be sized right and
installed properly. Flex duct should be supported every 4 to 6 feet. Flex duct
has high friction losses because of the coiled interior spring liner, so sharp
bends should be avoided. The diameter of flex duct must be adequately sized for
the airflow required, especially for runs longer than 12 feet.
Avoid pressurized rooms. If a room has a supply grille but no
return grille, the room can become pressurized. To avoid this problem, such
rooms need a low-resistance path for the return air. Verify that the door is
undercut by 11/2 to 2 inches or that transfer grilles are installed in a
partition between the room and the hallway.
How much will the suggested upgrades cost? The cost of upgrading a 100,000
Btu/h gas furnace from a single-stage unit to a two-stage unit with a variable
speed fan is between $750 and $900. A 3-ton air-source heat pump with a 10 SEER
efficiency rating can be upgraded to a two-stage unit with a 14.9 SEER rating
for an added cost of about $1,900.
Customers who choose the upgrades will reap returns on their investment: not
only increased comfort, but energy savings from the improved efficiency of the
equipment.
is vice president of H.B. McClure,
a heating and cooling contractor in Harrisburg, Pa.
Duct Tape Update
By now, most people know that regular hardware store duct tape is good for
almost anything but ducts. Duct tape has been used to make makeshift tow-chains
to pull vehicles from ditches, and for various emergency repairs on Apollo
space missions. When used on ducts, though, generic cloth duct tape fails when
the heat dries out the adhesive.
Perhaps you're wondering, then, "Why isn't there any industry standard for
duct tape?" It turns out that there is one -- at least for duct tape used on
flex duct and fiberglass duct.
 |
| Generic gray duct tape fails quickly when used to seal ducts (left).
Aluminum duct tape meeting UL 181 specifications (above), unlike most cloth
duct tape, is tested for adhesion strength under a variety of temperatures and
humidity levels. |
Underwriters Laboratories reports on its that UL first published a standard
for duct tape in October 1995. The standard, UL 181B, is called "Standard for
Safety for Closure Systems for Use with Flexible Air Ducts and Air Connectors,"
and covers duct tape for use on flex duct. Another standard, UL 181A, "Standard
for Safety for Closure Systems for Use with Rigid Air Ducts and Air
Connectors," covers duct tape for use with rigid fiberglass duct (duct board).
There are two types of UL 181A tape: heat-activated tape and pressure-sensitive
tape. In general, heat-activated tapes, which are sealed with a tool called a
heat seal iron, perform better than pressure-sensitive tapes.
According to the UL website, "The Standard requires that duct tape pass a
series of tests, including evaluations of tensile strength; peel adhesion
strength; shear adhesion strength under a variety of weights, temperatures and
humidity levels; long-term high-temperature effects; and surface burning
characteristics. UL also evaluates the tape for its ability to inhibit fungi
from growing."
If you want
a duct tape that actually works on ducts, look for the UL 181 designation,
which should be printed every 6 inches on the tape. These UL 181 duct tapes are
backed with aluminum foil, so they don't look like old-fashioned gray duct
tape.
For sealing sheet-metal duct, rather than flex duct or fiberglass duct, use
mastic, not tape. No standard exists for duct tape used on sheet-metal
duct.
by Jeri Donadee
This article has been provided by www.jlconline.com. JLC-Online is produced by the editors and publishers of The Journal of Light Construction, a monthly magazine serving residential and light-commercial builders, remodelers, designers, and other trade professionals.
|